Barrel fire SRP 50. Trunks are manual. Maximum blast distance

To supply water to the fire, fire nozzles of various modifications are used. The simplest ones create a continuous compact jet, some models allow the jet to be sprayed, as well as create a water curtain to protect against heat flow. special class represent barrels for creating air-mechanical foam from a foaming agent solution. NPO RUSARSENAL offers firefighters hand barrels various manufacturers in a wide range - from the simplest to the professional.

Range

Trunks are manual RS-25, RS-50, RS-50P, RS-70 are the simplest devices for creating a continuous compact jet. They are used, as a rule, for a complete set of fire cabinets.

For stationary mounting on a fire hose, modifications RS-50.01, RS-50.01P, RS-70.01 and RS-70.01P are used. They are used to complete fire cabinets, in cases where extension of the hose line is not required.

Name of indicator RS-25A RS-50A RS-50.01A RS-50.01P RS-70A RS-70.01A RS-70.01P
25 50 50 50 70 70 70
Working pressure, MPa 0,4-0,6
Water consumption at 0.4 MPa, l/s 3,6 7,4
Compact jet range at 0.4 MPa, m 28 32
Nozzle outlet diameter, mm 8 13 19
Overall dimensions, mm 205×60 270×100 190x62 190x62 315×128 190×78 190x62
Weight, kg, no more 0,3 0,7 0,27 0,1 0,95 0,38 0,2

Fire barrels RSK-50, SRK-50, RSP-50, RSP-70 have the function of blocking the flow of water with the possibility of creating a continuous or sprayed jet with constant angle torches. Trunk RSKZ-70 allows you to form a protective water curtain that protects the shooter from the heat flow.

Trunks ORT-50 and ORT-50A are more modern and complex products, due to which they have extended functionality:

  • formation of a continuous or sprayed jet,
  • formation of low expansion foam (using a removable foam generator),
  • formation of a spectrum of various jets and their combinations,
  • high spray quality with a wide range of spray angles.

Specifications
Name of indicator RSP-50 RSP-70 RSK-50 RSKZ-70 SRK-50 ORT-50 ORT-50A
Nominal passage of the connecting head, mm 50 70 50 70 50 50 50
Working pressure, MPa 0,4-0,6 0,4-0,8
Water consumption at 0.4 MPa, l/s, not less

continuous jet

atomized jet

protective curtain

2,7 7,4 2,7 7,4 2,7 3,0 7,4
2,0 7,0 2,0 7,0 2,7 3,0 7,4
- - - 2,3 - 1,3 1,3
Jet range, m, not less than
solid
atomized
30 32 30 32 30 32 33
11 9 11 9 12 24 24
Spray jet flame angle, degrees, not less than
minimum

Maximum

40 40 40 40 25 60 60
- - 70 - 60 20 20
Protective curtain flame angle, degrees, not less than - - - 120 - 120 120
Outlet diameter, mm 12 19 12 19 12
Protective curtain torch diameter, m, not less than - - - 3 - 3,5 3,5
Overall dimensions, mm, no more 350×140 390×170 360×140 430×170 390×145 305×230* 305×230*
Weight, kg, no more 1,45 2,80 1,95 3,00 1,80 1,4* 1,4*

*without foam nozzle.

Quality

All barrels supplied comply with GOST and technical regulations on fire safety requirements (123-FZ dated July 22, 2008), have passed all stages of development, production, are certified in the prescribed manner and are mass-produced.

Manual fire nozzles RSP-50 are designed to extinguish fires with a compact or sprayed jet of water. They are used to complete internal fire hydrants in residential, public, administrative, industrial buildings and structures, as well as fire motor pumps.

Trunks can be used in areas with a temperate, tropical climate, placement category 1 according to GOST 15150-69.

Specifications

Main specifications are given in table. 1, information about non-ferrous metals - in table. 2.

The connection size of the RSP-50 barrel with a hose line is 50 mm.

Table 1

Name of parameters Norms for standard sizes
RSP-50
1. Working pressure, MPa 0,4 – 0,6
2. Water consumption, l s -1, not less than *:
- continuous jet 2,7
- spray jet 2,0
3. Range of the water jet (maximum for extreme drops), m., not less than *:
- continuous jet; 30
- spray jet. 11
4. Angle of the sprayed jet, rad (deg) *:
- minimal; -
- maximum. 0,70 (40)
5. Outlet diameter (nozzle), mm 12H11 (+0.11)
6. Overall dimensions (Fig. 1, 2), mm, not more than:
- height ( H); 150
- length ( L); 350
- width ( B). 155
Weight, kg, no more 1,4

* Value according to p.p. 2-4 are given at working pressure (0.4 +0.05) MPa.

** Value at minimum flame angle.

table 2

The manufacturer reserves the right to make changes to the design that do not affect the quality of the product.

Product composition and completeness

1.1. The barrels (Fig. 1) consist of a body 1, a connecting head 2, a closing device with a handle 3 and a nozzle 4 (adjustable nozzle for the RSK-50 barrel). At the request of the customer, the trunks can be additionally equipped with a shoulder strap.

1.2. A batch of barrels delivered to one address is completed with a passport combined technical description and operating instructions in accordance with GOST 2.601-2006.

Rice. 1. The design of the manual fire barrel RSP-50

Device and principle of operation

1.1. The design of the barrel allows the formation of a compact or sprayed jet at the outlet, which increases the efficiency of extinguishing fires and more efficiently uses the water supply.

The position of the handle 3 (Fig. 1) of the blocking device for blocking and forming a compact or sprayed water jet:

I position - the jet is blocked (closed);

II position - compact jet;

III position - sprayed jet.

Specifying Security Measures

1.1. It is forbidden to use trunks near open power lines located within the radius of action of a continuous jet.

1.2. It is forbidden to wear a shoulder strap (if present in the design) of the trunk attached to the hose line when lifting and working at height.

1.3. By the time the water is started, the barrel must be securely kept working.

Preparation of the product for work and work procedure

1.1. In preparation for work, the barrel should be securely connected to the hose line. Set the handle 3 (Fig. 1) of the barrel to the position necessary for the formation of a certain type of jet and direct it to the fire. Signal readiness for work.

Maintenance

1.1. After finishing work:

1.1.1. Flush the barrel clean water, dry the shoulder strap (if present in the design);

1.1.2. Check the tightness of the screw connections and, if necessary, tighten them to the stop.

1.2. Every shift check the technical condition of all parts (no cracks, dents, nicks, etc.).

1.3. Once a year, check the presence of grease on moving parts with threaded connection, rotating parts and rubber rings and, if necessary, treat with Litol-24 grease, GOST 21150-87.

1.4. Store in a warehouse in conditions that exclude the effects of precipitation, direct sunlight.

1.5. Before short-term or long-term storage, steel parts of the barrel must be subjected to anti-corrosion protection with conservation oil K-17 GOST 10877-76. Protection options VZ-1 GOST 9.014-78. The product protection period is up to 1 year. When the barrel is put into operation after storage, depreservation is not performed.

1.6. The barrels are packed in a container that provides protection for products during storage and transportation. By agreement with the consumer, the delivery of barrels can be carried out without packaging in containers, when transporting them in universal containers and bodies road transport, with the protection of products from mechanical damage.

Warranty

The manufacturer guarantees the compliance of the barrels with the requirements of TU 4854-003-95431139-2014, subject to the conditions of operation, transportation and storage set forth in the "Specifications".

The warranty period is set at 12 months from the date of putting the barrels into operation.

General information

Trunk RSP-50 designed to extinguish fires with a compact or sprayed jet of water with a variable spray angle. RSP-50 barrels are equipped with mobile fire extinguishing equipment, and internal fire hydrants can also be equipped with manual fire barrels RSP-50, RSK-50 DSTU 2112-92 (GOST 9923-93) PASSPORT RSP-50-00-00.PS, RSK- 50-00-00.PS.

Trunks RSP-50 until recently were one of the most common types of fire nozzles in the Russian Federation.

Manufacturer

Barrels are manufactured by many enterprises, but the products of OOO Novokhartsyzsky Machine-Building Plant are the most widely known.

Hydraulic characteristics

Jet typehead,
m
consumption,
l/s
Base
solid40 2,7
Sprayed with a spray angle of 40gr.40 2

Design features

The design of the barrel allows the formation of a compact or sprayed jet at the outlet, thereby increasing the efficiency of extinguishing fires and more efficiently using the water supply.

The position of the handle of the shutoff device for shutting off, forming a compact or atomized water jet:

  • I position - the jet is blocked;
  • II position - compact jet;
  • III position - sprayed jet;
  • IV position - the minimum angle of the torch;
  • V position - the maximum angle of the torch.

Specifying Security Measures

It is forbidden to use trunks near open power lines located within the radius of action of a continuous jet.

It is forbidden to wear the shoulder strap of the barrel connected to the hose line when lifting and working at height. By the time the water is started, the barrel must be securely kept working.

Barrel preparation for work

In preparation for work, the barrel should be securely connected to the hose line. Set the barrel handle to the position necessary for the formation of a certain type of jet and direct it to the fire. Signal readiness for work.

Maintenance

" style="border: solid 1px #CCCCCC; display:inline-block; width:250px">


3 - handle, 4 - nozzle, 5 - belt

1 - housing, 2 - connecting head,
3 - handle, 4 - nozzle, 5 - belt

After finishing work
  1. Rinse the barrel with clean clean water, dry the belt.
  2. Check the tightness of the screw connections and, if necessary, tighten them to the stop.
Every shift
  1. Check the technical condition of all parts (no cracks, dents, nicks, etc.)
Once a year
  1. Check the presence of lubrication on moving parts with a threaded connection, rotating parts and rubber rings and, if necessary, lubricate them with synthetic grease brand press grease C GOST 4366 - 76.
Store in a warehouse in conditions that exclude the effects of precipitation, direct sunlight.

Before short-term or long-term storage, steel parts of the barrel must be subjected to anti-corrosion protection with conservation oil K-17 GOST 10877-76.

Protection options VZ-1 GOST 9.014-78.

The product protection period is up to 1 year.

When the barrel is put into operation after storage, depreservation is not performed.

The barrels are packed in a container that provides protection for products during storage and transportation. By agreement with the consumer, the delivery of barrels can be carried out without packaging in containers, when transporting them in universal containers and bodies of road transport, with the protection of products from mechanical damage.

VNIIPO of the Ministry of Internal Affairs of Russia has developed manual fire nozzles RSP-50, RSK-50, RSP-70, RSKZ-70, devoid of these shortcomings.

They form continuous and atomized jets with a variable spray jet angle (RSK-50) and a water protective curtain (RSKZ-70), have a ball-type blocking device.

Designed for a working pressure of 0.4-0.6 MPa, they provide:

water consumption with continuous jet:

  • 2.7 l/s (RSP-50, RSK-50),
  • 7.4 l/s (RSP-70, RSKZ-70),

spray water consumption:

  • 2.0 l/s (RSP-50, RSK-50),
  • 7.0 l/s (RSP-70, RSKZ-70) and protective curtain 2.3 l/s.

Sometimes, when extinguishing a fire, stationary equipment cannot cope with the tasks that need to be solved as quickly as possible. This is largely due to the main disadvantage of such systems - the complete lack of mobility. That is why manual fire nozzles are the actual fire equipment that is on the market today.

In this article, we will consider the most popular models of manual fire nozzles, their functional features and principles of operation.

Device

The structural component of the universal barrels for manual use makes it possible to use both a continuous flow of fire extinguishing material and a sprayed one.

The RSK-50 manual barrel includes such elements as:

  • frame;
  • stopcock;
  • nozzle on the trunk;
  • connecting (integrated) head.

Structural elements of the RSK-50 barrel

The handle of a plug faucet is the main tool that controls the jet that is given out under pressure. By changing the position of the handle relative to the barrel itself, you can change the type of jet coming out of the barrel hole. The main types of water or foam mixture at the outlet:

  • solid stream;
  • spray stream;
  • protective curtain.

Depending on the case, it is possible to change the type of fire extinguishing material supplied without violating the functionality of the entire device.

The plug faucet handles on the other two models mentioned above have exactly the same functions.

When the handle 4 of the plug valve 3 is positioned along the axis of the body 5, the liquid flow passes through the central hole and then exits the nozzle 12 in the form of a compact jet. When the handle is turned by 90 0, the central hole is blocked and the liquid flow from the cavity 8 of the hollow plug of the tap through the holes 7 and 10 enters channels 1, 2 and 9. Through the tangential channels 11, the liquid enters the central atomizer and leaves it in a swirling flow, which under by the action of centrifugal forces, when exiting the nozzle, it is sprayed, forming a torch with an opening angle of 60 0 . A similar principle of operation is incorporated in the design of universal trunks RSP-50 and RSP-70. Trunk RSKZ-70 allows, in addition, to additionally form a protective water curtain.

Maximum blast distance

continuous jet:

  • 30 m (RSP-50, RSK-50),
  • 32 m (RSP-70, RSKZ-70);

spray jet:

  • 11 m (RSP-50, RSK-50),
  • 15 m (RSP-70, RSKZ-70);

effective spray range:

  • 5 m (RSP-50, RSK-50)
  • 10 m (RSP-70, RSKZ-70), the average irrigation intensity is 0.14 and 0.2 l / m 2, respectively.

Barrel weight: 1.5 kg (RSP-50), 1.9 kg (RSK-50, RSP-70) and 2.4 kg (RSKZ-70).

Fire tests of barrels under conditions close to those of a real fire were carried out in Perm and Samara at special test sites.

Extinguishing with sprayed water jets of diesel fuel, flammable combustible liquids with a flash point below 0 degrees, as well as a trap product, which is an oil recovery with a specific gravity of 0.8 t / m 3 and a flash point of +28 degrees, showed a higher efficiency of new manual fire hoses compared to existing ones.

The proposed trunks are recommended for use in the configuration of mobile fire equipment, as well as (trunks RSP-50, RSP-70) internal fire hydrants in residential, public, administrative, industrial buildings and structures.

To complete mobile fire equipment and equipped with hoses d 38 mm, a manual fire nozzle RSP-38 has also been developed, which has the following main parameters:

  • working pressure - 0.4-0.6 MPa;

water consumption:

  • continuous jet - 1.8 l / s; sprayed - 1.5 l / s.

jet distance:

  • solid - 25 m; sprayed - 11 m.

Specifications

Indicators Universal hand fire nozzles With protective curtain
RSK-50 RSP-50 RSP-70 RSKZ-70
Water consumption at a pressure of 0.4 MPa, l/s:
continuous jet 2,7 2,7 7,4 7,4
spray jet 2,7 2,0 7,0 7,0
protective jet - - - 2,3
Jet range at a pressure of 0.4 MPa, m:
continuous jet 30 30 32 32
spray jet 12 11 15 15
Protective curtain flame angle, deg - - - 120 0
Protective curtain flame diameter, m - - - 6
Connecting fittings GM-50 GM-70
Barrel weight, kg 2,2 1,6 2,8 3,0